AH6500: Sizing Table - Wine Cellars 1500-2000 cu ft

55°F Cooling Capacity1

Cooling Unit Output

Low Fan Speed
4923 BTUH
Decibels2
-ECX 38 / 43
-ECC 47 / 43

Medium Fan Speed
5350 BTUH
Decibels2
-ECX 44 / 50
-ECC 51 / 43

High Fan Speed
5771 BTUH
Decibels2
-ECX 52 / 55
-ECC 59 / 55

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

1500

Cubic Feet

70°F460843464188
75°F482944804268
80°F504846134349
85°F526947464429
90°F549048794510
95°F571150144591

1750

Cubic Feet

70°F514148604691
75°F537650024775
80°F561251444861
85°F(5849)52884949
90°F(6085)54315035
95°F(6324)55765124

2000

Cubic Feet

70°F(5861)55565372
75°F(6116)57115466
80°F(6373)(5866)5558
85°F(6630)(6022)5653
90°F(6888)(6178)5748
95°F(7146)(6335)(5844)

60°F Cooling Capacity1

Cooling Unit Output

Low Fan Speed
5532 BTUH
Decibels2
-ECX 38 / 43
-ECC 47 / 43

Medium Fan Speed
5981 BTUH
Decibels2
-ECX 44 / 50
-ECC 51 / 43

High Fan Speed
6421 BTUH
Decibels2
-ECX 52 / 55
-ECC 59 / 55

Cellar Size

Ambient
Temperature
Thermal Load (BTUH)
R12R19R30

1500

Cubic Feet

70°F405538243685
75°F425039423756
80°F444240593827
85°F463741763898
90°F483142943969
95°F502644124040

1750

Cubic Feet

70°F452442774128
75°F473144024202
80°F493945274278
85°F514746534355
90°F535547794431
95°F556549074509

2000

Cubic Feet

70°F515848894727
75°F538250264810
80°F560851624891
85°F583452994975
90°F606154375058
95°F628855755143

The upper table is shaded to show how the AH6500 air handler cooling system will work at maintaining 55°F, and the lower how the AH6500 air handler cooling system will work at maintaining 60°F, inside the wine cellar using various fan speeds under various thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar.

CellarPro AH6500 wine cooling units are designed to maintain optimal wine storage temperatures in wine cellars up to 1750 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 110°F. For more information, click on our performance and test data.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.

(1) The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

(2) The decibels are listed for the evaporator / condensing unit, both ducted.